Shopping security
The Honeywell 900A01-0202 serves as a high-density, universal analog input interface for the HC900 Hybrid Control System. This module accepts eight isolated inputs, allowing users to mix and match signals including Thermocouples, RTDs, mA, Volts, and Slidewire sensors on a single card. It converts these critical field variables into precise 16-bit digital values for the controller CPU. We supply this unit as 100% Brand New in its original factory packaging, ensuring maximum field longevity and compliance with original manufacturer specifications.
| Attribute | Specification Details |
| Channels | 8 Isolated Analog Inputs |
| Input Types | mV, V, T/C, RTD (Pt100), Ohms, mA, Slidewire |
| Resolution | 16-Bit |
| Accuracy | ±0.1% of Full Scale |
| Galvanic Isolation | 400 VDC point-to-point; 1K VDC to logic |
| Input Impedance | 10 MΩ (T/C, mV); >1 MΩ (Volts); 250 Ω (mA) |
| Noise Rejection | Series Mode >60dB; Common Mode >130dB @ 120VAC |
| Sampling Rate | Typical 100 ms per channel (Configurable) |
| Operating Temp | 0°C to +60°C |
| Weight | 0.4 kg (0.6 lbs) |
Universal Channel Configuration: The module eliminates the need for multiple specialized cards. Engineers assign different signal types (e.g., a Type K thermocouple on channel 1 and a 4-20mA pressure transmitter on channel 2) via software, reducing spare parts inventory.
Superior Noise Immunity: With a common mode rejection ratio of >130dB, the 900A01-0202 maintains signal integrity in electrically noisy environments. It effectively filters out interference from high-voltage equipment and motors commonly found in power generation and chemical plants.
Advanced Galvanic Isolation: Robust 400 VDC point-to-point isolation prevents ground loops and protects the system backplane from field-side electrical faults. This architectural safeguard ensures that a failure on one sensor does not compromise the entire I/O rack.
Cold Junction Compensation (CJC): For temperature applications, the module performs high-accuracy internal cold junction compensation. This feature provides stable temperature readings even as the ambient temperature within the control cabinet fluctuates.
Smart Diagnostics: The module utilizes a current pulse for Thermocouple Break Detection. It alerts the control system immediately upon sensing a sensor failure, enabling rapid maintenance and preventing process downtime.
Can I mix RTDs and 4-20mA signals on the same 900A01-0202 module?
Yes. The 900A01-0202 supports universal inputs. You can configure each of the eight channels independently for any supported signal type via the HC900 configuration software.
What is the isolation level between channels?
The module provides galvanic isolation of 400 VDC point-to-point. Note that RTDs are isolated in pairs (the IRTD is common to two inputs), while other signal types enjoy full individual isolation.
How does the module handle over-range signals?
The 900A01-0202 permits a +/- 10% over-range limit for linear ranges (Volts) and +/- 1% for non-linear ranges (T/C, RTD) before reporting an out-of-range error to the CPU.
Is this module "Hot-Swappable"?
Yes, within the HC900 architecture, you can remove and replace the 900A01-0202 under power, provided you follow the standard safety procedures for the ControlEdge 900 platform.
Ships within 48 hours · Estimated delivery Jun 21 - Jun 26